ENERGY CUT OFF (E.C.O.)
CONNECTION
A five-function valve uses the two E.C.O. termi-
nals that are connected to the magnetic assembly
where the thermocouple connects to the 36C
valve line interrupter.
Connect the leads from the E.C.O. terminals to
the E.C.O. device on the furnace. Test the E.C.O.
device for continuity. If there is no continuity, the
power unit will not hold in. See figure 5.
If the furnace does not have an E.C.O. device,
jumper the E.C.O. terminals on the valve with the
jumper lead provided.
PILOT GAS ADJUSTMENT
If the pilot flame is low and does not engulf the
bulb of the mercury flame sensor, the system will
not energize the main valve. If pilot gas pressure
is too high, gas will sputter past the ignition elec-
trode, and may not ignite. High pilot gas pressure
may also cause the flame to lift off the burner,
causing the flame sensor bulb to sense "low" heat.
To adjust the pilot gas pressure, remove the cover
screw (see fig. 8). To REDUCE pilot pressure, turn
the pilot adjust screw (beneath the cover screw)
clockwise. To INCREASE pilot pressure, turn the
pilot adjust screw counterclockwise. Replace and
tighten cover screw.
Figure 8. Pilot Gas Adjustment
Figure 8. Pilot Gas Adjustment
Pilot adjust
cover screw
Gasket
Pilot
adjust
screw
THERMOCOUPLE CONNECTION
(24 VAC AND 120 VAC MODELS)
The thermocouple connection should be clean to
ensure good electrical contact.
Run the thermocouple nut into the power unit
tapping as far as possible by hand. Then use a
small wrench to set the nut with a 1/4 to 1/2 ad-
ditional turn. Do not overtighten.
PILOT GENERATOR CONNECTION
(FOR .750 VAC MODELS)
Be sure the pilot generator is completely engaged
into the pilot burner.
Be sure that the two terminals from the pilot gen-
erator are securely tightened beneath the proper
screws on the valve.
Connect the power unit lead to the high limit and
the high limit to the TH-PG terminal.
PRESSURE REGULATOR

ADJUSTMENT

The pressure regulator has been factory adjusted
(see control label for specific setting). Although
additional adjustments will not normally be nec-
essary, you may adjust the regulator. Do not force
the adjusting screw beyond the limits that it can
easily be adjusted.
1. Energize valve to ignite main burner.
2. Remove "Reg. Adj." cover screw (see fig. 9).
3. To DECREASE outlet pressure, turn the adjust-
ing screw (beneath the cover screw) counter-
clockwise. To INCREASE outlet pressure, turn
the adjusting screw clockwise.
4. Replace the cover screw. Cycle the valve two or
three times to verify regulator setting.
Regulator adjusting
cover screw
Figure 9. Pressure Regulator Adjustment
Figure 8. Pressure regulator adjustment
INSTALLATION
ADJUSTMENT
Pilot adjust
cover screw
5