CHAMP
VMV Hi –Lumen 13L-25L series
®
Installation & Maintenance Information
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
APPLICATION
Champ® VMV Series Luminaires are suitable for use in
the following hazardous (classified) areas as defined by the
National Electrical Code (NEC®).
Refer to the luminaire nameplate for specific classification
information,
VMV:
NEC/CEC
• Class I, Division 2, Groups A, B, C, D
• Class II, Groups E, F, G
• Simultaneous Presence
• Wet Locations, Type 4X
• IP66
UL Standards
• UL 844 Hazardous (Classified)
• UL1598 Luminaires, UL1598A Marine
• UL8750
• UL50, UL50E
• CUL Certified to CSA C22.2 No. 137
Input Voltage:
UNV1 100-277 VAC 50/60 Hz
108-250 VDC
0.48 -2.35A
130 - 235 Watts
IEC/ATEX Standards
• IEC 60079-0:2011 / EN 60079-0:2012
• IEC 60079-15:2010 / EN 60079-15:2010
• IEC 60079-31:2008 / EN 60079-31:2009
• IEC 60529:2001 / EN 60529:2001
• IEC 60598-1:2008 / EN 60598-1:2008
• IEC 60598-2-1:1979/EN 60598-2-1:1989
WARNING
To avoid the risk of fire or electric shock, this product
should be installed, inspected, and maintained by a
qualified electrician only, in accordance with all applicable
electrical codes.
WARNING
To avoid electric shock:
Be certain electrical power is OFF before and during
installation and maintenance.
Luminaire must be supplied by a wiring system with an
equipment grounding conductor.
To avoid injury or burn:
Make sure lens and housing are cool when performing
maintenance.
Note: Only the LED subassembly and mounting cover joints
may be serviced. All other joints can only be serviced by
Crouse-Hinds.
IF 1701 • 04/14
Copyright © 2014, Eaton's Crouse-Hinds Business
maximum ambient temperature suitability, and
corresponding operating temperature (T-Code).
Luminaire construction is designed for use indoors and
outdoors in marine and wet locations, where moisture, dirt,
corrosion, vibration, and rough usage may be present.
Fixture Markings
• 14 ATEX 1324722X
*
• 14 ATEX 2274231X
• IECEx UL 14.0031X
VMV13L – 17L
Ex nA nR IIC T6 Gc -40°C to +40°C
Ex nA nR IIC T5 Gc -40°C to +55°C
Ex tb IIIC T66°C Db IP66 -40°C to +40°C
Ex tb IIIC T81°C Db IP66 -40°C to +55°C
*
II 3 G Ex nA nR IIC T6 Gc -40°C to +40°C
*
II 3 G Ex nA nR IIC T5 Gc -40°C to +55°C
II 2 D Ex tb IIIC T66°C Db IP66 -40°C to +40°C
II 2 D Ex tb IIIC T81°C Db IP66 -40°C to +55°C
VMV21L –25L
Ex nA nR IIC T6 Gc -40°C to +40°C
Ex nA nR IIC T5 Gc -40°C to +55°C
Ex tb IIIC T71°C Db IP66 -40°C to +40°C
Ex tb IIIC T86°C Db IP66 -40°C to +55°C
*
II 3 G Ex nA nR IIC T6 Gc -40°C to +40°C
*
II 3 G Ex nA nR IIC T5 Gc -40°C to +55°C
II 2 D Ex tb IIIC T71°C Db IP66 -40°C to +40°C
II 2 D Ex tb IIIC T86°C Db IP66 -40°C to +55°C
WARNING
To avoid explosion:
Make sure the supply voltage is the same as the
luminaire voltage.
Do not install where the marked operating temperatures
exceed the ignition temperature of the hazardous
atmosphere.
Do not operate in ambient temperatures above those
indicated on the luminaire nameplate.
Use proper supply wiring as specified on the luminaire
nameplate.
All gasket seals must be clean.
Before opening, electrical power to the luminaire must
be turned off. Keep tightly closed when in operation.
To reduce the risk of ignition due to electrostatic
discharge, avoid contact with the luminaire while
explosive atmosphere is present Clean only with damp
cloth.
FIELd ASSEMbLEd FIXTURES
Champ
VMV Series Lighting Fixtures, 40-120 Watt
®
IF 1701
INSTALLATION
1. Mount the cover module in its support position.
• Ensure mounting location and method is adequate to
support fixture weight
• Ceiling and wall mount: mark and drill desired location on
mounting surface. Secure with 1/4" (6mm) bolts or lag
screws (not provided).
• Pendant, cone, stanchion mount: securely thread onto
the appropriate NPT size conduit. Tighten set-screw
located in the conduit hub. See Figure 1.
• Crouse-Hinds HTL thread lubricant must be added to
the conduit threads to prevent water from entering the
fixture.
2. Verify sufficient HTL lubricant is on conduit plugs
(recommend approximately 1/8" bead around the first thred
of plug) and that all unused conduit entries on the cover
module are closed with lubricated plugs.
3. Plugs must be installed with at least five (5) full threads
into the cover module conduit entries.
4. Torque plugs to 42-52 ft.-lbs. (57-71 N-m) for ¾" and 20
mm plugs, and 58-68 ft.-lbs. (79-92 N-m) for 1" and 25 mm
plugs.
Page 1
IF 1701 • 04/14
MOUNTING MOdULE NOTES:
- 2: indicates 3/4" NPT thread
- 3: indicates 1" NPT thread
- 5: indicates 1-1/2" thread
- 20: indicates 20 mm thread
- 25: indicates 25 mm thread
- Pendant, angled, ceiling, and stanchion
mounts have one (1) conduit entry;
ceiling and wall mounts have five (5)
conduit entries
Set-screw
5. Pull field wiring into cover module. Connect the supply
wire leads to the terminal block or to wire leads per the
wiring diagram and using methods that comply with all
applicable codes.
6. Check that all electrical connections tightened and secure.
7 . Verify all wires are safely and neatly inside driver housing
and not on top of wire terminal, close the driver housing
onto cover module ensuring no wires are pinched in the
gasket joint.