Champ VMVL and PVML LED luminaires
Installation & maintenance information
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
APPLICATION
Champ
VMVL luminaires are suitable for use in certain hazardous
®
(classified) areas as defined by the National Electrical Code (NEC
Champ
PMVL luminaires are not suitable for use in these NEC
®
classified areas.
VMVL:
Input voltage:
IEC/ATEX standards
UNV1
• IEC 60079-0:2011, 6th Edition / EN 60079-0:2012
• IEC 60079-7:2010, 5.1 Edition / EN 60079-7:2015
• 100-277 VAC, 50/60 HZ NEC
• IEC 60079-31:2008, 2nd Edition / EN 60079-31:2014
• 100-240 VAC, 50/60 HZ EN/IEC
• IEC 60529:2001 / EN 60529:2001
• 127-250 VDC
• IEC 60598-1:2008 / EN 60598-1:2008
• IEC 60598-2:2008 / EN 60598-2:2008
NEC/CEC
• IEC 60079-18:2017, 4.1 Edition / EN 60079-18:2015 +
• Class I, Division 2, Groups A, B, C, D
A1:2017
• Class II, Groups E, F, G
• Class III
Luminaire markings
• Class I, Zone 2 AEx ec mb IICT*GC
• IECEx UL 13.0052X
• Zone 21 tb IIIC
• DEMKO 13 ATEX 1305741X
• Simultaneous Presence
• DEMKO 13 ATEX 1475031X
• Wet Locations, Type 4X
100-277 VAC/127-250 VDC (UNV1 base luminaire
UL standards
only)
• UL 844 Hazardous (Classified)
II 3 G
• UL1598 Luminaires, UL1598A Marine
II 3 G
II 3 G
CSA standard
II 2 D
• CSA C22.2 No. 137
II 2 D
II 2 D
For EMC compliance:
If the dimming interface of the LED driver are connected to an external dimmer which is not provided with the luminaire, a ferrite core must be
used on the input and dimming lines. Approved ferrite cores are Fair-Rite P/N 0431167281.
WARNING
To avoid the risk of fire, explosion or electric shock, this product
should be installed, inspected and maintained by a qualified
electrician only, in accordance with all applicable electrical codes.
WARNING
To avoid electric shock:
Be certain electrical power is OFF before and during installation and
maintenance.
Luminaire must be supplied by a wiring system with an equipment
grounding conductor.
To avoid burning hands:
Make sure lens and housing are cool when performing
maintenance.
INSTALLATION
MOUNTING:
1.
Mount the cover module in its support position.
• Ceiling and wall mount: mark and drill desired location on mounting
surface. Secure with 1/4" (6mm) bolts or lag screws (not
provided).
• Pendant, cone, stanchion mount: securely thread onto the
appropriate NPT size conduit. Tighten set screw located in the
conduit hub. See Figure 1.
• Eaton's Crouse-Hinds HTL thread lubricant must be added to the
conduit threads to prevent water from entering the luminaire.
Open
FIGURE 1
hinge
Set screw
Ground wires
IF 1882 • 07/19
Copyright © 2019, Eaton's Crouse-Hinds Division
Refer to the luminaire nameplate for specific classification information,
maximum ambient temperature suitability and corresponding operating
temperature (T-code).
).
®
Luminaire construction is designed for use indoors and outdoors in
marine and wet locations, where moisture, dirt, corrosion, vibration
and rough usage may be present.
PVML:
Input voltage:
UNV1
• 100-277 VAC, 50/60 HZ
• 127-250 VDC
Certifications & compliances
• Wet location, Type 4X
• IP66
UL standards
• UL1598 Luminaires, UL1598A
Marine
• UL8750
• UL50, UL50E
CSA standard
• CSA C22.2 No. 250.0-08
EX ec mb IIC T5 Gc -40°C to +40°C
EX ec mb IIC T5 Gc -40°C to +55°C
IEC standard
EX ec mb IIC T4 Gc -40°C to +65°C
• IEC 60598
Ex tb IIIC T72°C Db -40°C to +40°C
Ex tb IIIC T87°C Db -40°C to +55°C
Ex tb IIIC T92°C Db -40°C to +65°C
WARNING
To avoid explosion:
Make sure the supply voltage is the same as the luminaire voltage.
Do not install where the marked operating temperatures exceed
the ignition temperature of the hazardous atmosphere.
Do not operate in ambient temperatures above those indicated on
the luminaire nameplate.
Use proper supply wiring as specified on the luminaire nameplate.
All gasket seals must be clean.
Before opening, electrical power to the luminaire must be turned
off. Keep tightly closed when in operation.
To reduce the risk of ignition due to electrostatic discharge, avoid
contact with the luminaire while explosive atmosphere is present.
Clean only with damp cloth.
WIRING:
1.
Pull field wiring into cover module.
2.
Close all unused conduit entries with conduit plugs provided. To
prevent galling and to ensure watertightness, lubricate conduit
plugs with Eaton's Crouse-Hinds HTL lubricant before installing,
and secure wrench-tight with at least five (5) full threads engaged
(42-52 ft.-lb. for 3/4" plugs, and 58-68 ft.-lb. for 1" plugs).
3.
Hang LED luminaire on the cover module hinge hook.
4.
Connect supply wires to luminaire wire leads or terminal block per
the attached wiring diagrams using methods that comply with all
applicable codes. See Figure 2. Tighten all electrical connections.
5.
Close driver housing onto cover module, making sure that all wires
are safely inside driver housing. Tighten captive closing screw to
30 in.-lbs. (3.4 N-m). Ensure two (2) bosses on driver housing are
in contact with cover module.
6.
Turn power on.
IF 1882
Page 1
IF 1882 • 07/19
FIGURE 2
Copyright © 2019, Eaton's Crouse-Hinds Division
Page 2