Analog Voltage and Current Input and Output Ranges
Analog Voltage Input Range
–24V dc
Underrange
Analog Current Input Range
–21 mA
–50 mA
Underrange
Note: The analog voltage inputs are protected to withstand the application of ±24V dc
without damage to the controller. The analog current inputs are protected to withstand the
application of ±50 mA without damage.
Analog Voltage Output Range
0V dc
Analog Current Output Range
4 mA
Note: The analog outputs are protected to withstand the short circuiting of the voltage or
current outputs without damage to the controller.
Publication 1761-IN001B-EN-P - July 2007
–10.5V dc
Operating Range
Operating Range
Operating Range
Operating Range
10.5V dc
21 mA
20 mA
24V dc
Overrange
50 mA
Overrange
10V dc