G
®
AERASGARD
RPS - SD ⁄ RFTM - PS - xx
Schematic diagram
1 2 3
Outputs
4
fine dust [ g/m
3
]
5
temperature [°C]
6
humidity [% r.H.]
relay
switch
point
13
11
12
SET REL.
NC = Normally Closed
COM = Common
NO = Normally Open
DIP switch
Fine dust ( PM ) Measuring range
3
0...50 µg/m
0...100 µg/m
3
(default)
0...300 µg/m
3
3
0...500 µg/m
Fine dust ( PM ) Particle size
PM 2.5 (default)
PM 10
CO2 content
0...2000 ppm (default)
0...5000 ppm
CO2 automatic zero point
deactivated
activated (default)
Relay assignment
CO2 (default) 600...1900 ppm / 900...4700 ppm
Fine dust
10 %...95 % of measuring range
Temperature
+5...+48 °C
Humidity
10...95 % r.H.
Output
Voltage 0 -10 V (default)
Current 4...20 mA
Note: DIP 5 is not assigned !
RFTM - PS - CO2 - W
Plug for
display
DIP
ON
ON
ON
1 2 3 4 5 6 7 8 9
PS
CO2
Mode
ZERO
OFFSET
°C
r.H.
CO2 CO2
RFTM - PS - x x
DIP 1 DIP 2
OFF
O N
OFF
O N
DIP 7 DIP 8
OFF
O N
OFF
O N
Schematic diagram
1 2 3
DIP switch
Fine dust ( PM ) Measuring range
3
OFF
0...50 µg/m
OFF
0...100 µg/m
3
(default)
O N
0...300 µg/m
3
3
O N
0...500 µg/m
Fine dust ( PM ) Particle size
DIP 3
O N
PM 2.5 (default)
OFF
PM 10
DIP 4
OFF
O N
DIP 6
OFF
O N
OFF
OFF
O N
O N
DIP 9
OFF
O N
12
Rev. 2021 - V11
RPS - SD
DIP
ON
1 2 3
PS
RPS - SD
DIP 1 DIP 2
OFF
O N
OFF
O N
OFF
OFF
O N
O N
DIP 3
O N
OFF