5 COMMISSIONING OF EZ LOGIC ACTUATOR
5.1 PRODUCT DESCRIPTION
According to the reference, the EZ LOGIC control can work with single-phase, 3-phase or 24VDC.
Moreover, EZ LOGIC features a local command, a 7-segment display giving a percentage of opening
and several LED for signaling.
EZ LOGIC control can be proposed in two versions:
ON/OFF: Only the 'valve opened' and 'valve closed' positions are managed. The electronic board
receives a command by 'dry contacts' or by 'voltage' to 'Open' , 'Close' or 'Stop' . These actuators can
be identified on the rating plate by the following code:
EZxxxx FL XX 123 A0 are equipped with ON/OFF board
POSITIONING: The EZ LOGIC control receives an analog input signal (4/20mA as standard, 0/20mA
or 0/10VDC are also possible) and manages the valve positioning. A position feed-back is given to
the remote command. These actuators can be identified on the rating plate by the following code:
EZxxxx KL XX 123 A0 are equipped with positioning board
5.1.1 Keyboard
1
8
6
3
5 sec.
8
They work exclusively as ON/OFF
They can also work as ON/OFF
Description
1.
7-segment display
9
(Percentage of opening, user's indications)
2.
Selection key LOCAL / REMOTE and Escape
10
3.
CLOSING and 'Go down' key
4.
STOP and validation key
2
5.
OPENING and 'Go up' key
6.
VALVE CLOSED Led (Possible customization
7
Green/Red), flashing during closing operation)
4
7.
VALVE OPENED Led (Possible customization Red/
Green) blinking during opening operation)
5
8.
SETTING Led. Light is ON in setting mode.
9.
ALARM Led. Light is ON in case of alarm and fault
code is displayed
10.
LOCAL Led. Light is ON in local mode
Local command Inhibition
The keypad is protected against unexpected local command by a
local command inhibition.
This function is activated automatically after 1 minute without tou-
ching the keypad or by pressing the STOP key for 5 seconds.
When local control is locked, the display will show a key
To unlock, press the STOP key for 5 seconds.
.