5.5.4 Description of 'read configuration' menu (
-
To entrer Read Configuration menu, move in the main menu like described in chapter 5.5.2 and
press OK (Stop) when
-
Go UP and DOWN to reach the sub-menus
-
Press OK to enter the sub-menus
-
Read the setting of the local command.
-
Read the setting of the proportional command.
If proportional command is ON, press OK to read the type of input signal.
If the selected input signal is 4/20, press OK in order to read the failsafe position.
You can return to the upper menu by pressing Esc. (Escape).
-
Read the nominal voltage (Single phase or 24VDC) or (3-phase)
-
Read the closing direction (Close clockwise) or (Close Counter- ClockWise)
5.5.5 Read the existing alarm codes (
-
To enter the Read Error menu, move in the main menu like described in chapter 5.5.2 and press
OK (Stop) when
-
Go UP and DOWN to read the codes
-
If there's no alarm, display is
Code
---
E01
E02
E03
E04
E05
E06
E07
is displayed.
is displayed.
Alarm
No fault found
Max torque reached
Thermal overload
Loss of one phase
Loss of 4/20mA input signal
Rotor is jammed
Position sensor in fault
Torque sensor in fault
English
)
)
Condition
Not available on EZ4 à EZ15
For 3-phase supply
Not applicable with 0/20mA
Not available on EZ4 to EZ15
17