5.2.2 Power supply
Connect the power board according to the voltage indicated
on the rating plate.
-
3-Phase : L1/ L2 / L3 / PE
-
Single-phase : L / N / PE
-
24VDC : + / - / PE
5.2.3 Remote command
The EZ LOGIC actuator's remote control system can be operated using an external voltage supply
or dry contact command (internal 24VDC).
The input circuits are fully opto-isolated. The pulse command system requires four connecting wires
on the client terminal strip: Common, stop, open and close. If the stop push-button is not used, do
not connect the STOP wire, open (or close) switch must be maintained to operate the actuator.
Dry contact command
In case of dry contact control, a jumper must be fitted across terminal 9-10.
8
9
GND
10
+24V
11
OPEN
12
CLOSE
13
14
Pulse remote commande
(self-holding)
Voltage command
Remote control can use either in AC or DC voltage.
Use common terminal 9 for low voltages from 10 to 55V.
Use common terminal 8 for voltages from 90 to 250V.
Caution: Never connect voltage sources above 55V on common terminal 9
8
9
10
11
OPEN
12
CLOSE
13
14
To remove self holding of the board, don't connect 14
10
STOP
10 - 55V ~
+
-
STOP
+
-
PE
8
9
GND
10
+24V
11
OPEN
12
CLOSE
13
14
Maintained remote command
(without self-holding)
90 - 250V ~
8
9
10
11
OPEN
12
CLOSE
13
14
L3 L2/L L1/N PE
+
-
STOP