Start-up and adjustment
Introduction
Electric
connection
Optimum process
Procedure
28
This section will guide you through the start-up and adjustment of AD 120 B.
The dehumidifier is supplied with a 2-metre connection cable with a connector for
230 V, 1N + PE.
The connected output is 0.78 kW, fuse 10A.
The regeneration air flow must always be set to 35 m3/h.
Note
The capacity of the dehumidifier does not increase if the regeneration air flow is set
higher. If the regeneration air flow is set too low, the heating element may be damaged
and this will result in a large amount of condensed water in the regeneration air outlet.
Follow this procedure for start-up and adjustment of the appliance:
Step
1
Check that all ducts/pipes are correctly connected and the clips are tightened
2
Check that the filter is in place
3
Connect the plug to 230 V AC
4
Set the toggle switches (red and black) to
the required position:
Red
Pos. 0: Dehumidifier
disconnected
Pos. I: Dehumidifier
switched on
5
The regeneration air flow should be adjusted using a damper (not included)
The dehumidifier is now ready for operation.
Action
Black
Pos. MAN:
Manual operation
Pos. HYG:
Hygrostat-operated
Continued overleaf