Start-up and adjustment,
Constant fan opera-
This operation mode is only used when a hygrostat is connected!
tion for hygrostat-
When the dehumidifier is controlled by a hygrostat it may in some cases be desirable to
controlled dehumidi-
let the fan run no matter whether the dehumidifier is running or not. In such cases fan
fier
and rotor are in operation continuously. The hygrostat switches the heating element on
and off in accordance with the set value. When the heating element is switched off there
is no dehumidification.
In order to obtain this operation mode, the wiring has to be changed as follows, please
see the section "Power circuit", page 76:
continued
Step
1
Dismantle the top cover
2
Change the connection between terminal 6 and 7 at the bottom of the multi-
ple plug, thus creating a connection between terminal 3 and 7. REMEMBER to
tighten the conductor that remains in terminal 6 (see numbering at the inside
of the top cover)
Action