Operating Instructions
Passive DC signal isolator SIRAX TI 807
Contents
7. Mounting ................................................................... 15
9. Maintenance ............................................................. 15
1. Read first and then ...
The proper and safe operation of the device
assumes that the Operating Instructions are
read carefully and the safety warnings given
in the Sections
5. Mechanical coding of the
plug-in module
6. Electrical connections
7. Mounting
are observed.
The device should only be handled by ap-
propriately trained personnel who are famil-
iar with it and authorised to work in electrical
installations.
2. Scope of supply
Signal isolator (1) (incl. plugged sets of codes)
Order Code: Significance of the digits
807 - 6 x x x
1
Standard (non-Ex)
2
[EEx ib] IIC, input signals intrinsically safe
6
[EEx ia] IIC, output signals intrinsically safe
2
2 channels (interfaces)
3
3 channels (interfaces)
0 0 ... 20 mA
2 0 ... 10 V, 2 channels
3 0 ... 10 V, 3 channels
1 coding camb (2)
(for coding the backplane SIRAX BP 902)
1 type examination certificate (3), (for Ex version devices
only)
1 Operating Instructions (4) in three languages: English,
French and German
12
(4)
(1)
Betriebsanleitung
Passiver DC-Signaltrenner SIRAX TI 807-6
Mode d'emploi
Séparateur galvanique passif
SIRAX TI 807-6
Operating Instructions
Passive DC signal isolator SIRAX TI 807-6
V 644-6 B d-f-e
107 947
1000-04.97
Aargauerstrasse 7
CH-5610 Wohlen/Switzerland
Telefon +41 56 618 21 11
Telefax +41 56 618 24 58
Camille Bauer AG
Telex 827 901 cbm ch
Fig. 1
3. Brief description
The signal isolator SIRAX TI 807 serves to electrically insulate
two or three analogue DC signals in the range 0...20 mA
which depending on version is then converted to a current or
voltage signal (0...20 mA or 0...10 V). It does not require a
separate power supply.
4. Technical data
Input signal E
DC current signal I
:
0...20 mA
E
Max. perm. current:
50 mA
Voltage limiter:
Non-Ex version: 27 V, ± 5%
(with zener diode)
Ex version: 18 V, ± 5%
Output signal A
(DC current or DC voltage)
DC current signal I
:
0...20 mA
A
Voltage drop U
:
V
< 2.8 V
for the standard (non-Ex) version
< 4.7 V
for Ex versions
(input signals "intrinsically safe")
< 6.3 V
for Ex versions
(output signals "intrinsically safe")
(2)
(3)