THE INDOOR UNIT INSTALLATION
10
!
CAUTION
Installation Information For Declination
- Install declination of the indoor unit is very important for the drain of the convertible type
air conditioner.
- Minimum thickness of the insulation for the connecting pipe shall be 10mm.
- If the Installation Plates are fixed to horizontal line, the indoor unit after installing will be
declined to the bottomside.
- The unit must be horizontal or inclined at angle.
- The inclination should be less than or equal to 1° or in between 10 to 20mm inclined in drain
direction as shown in fig.
- The unit must be declined to the bottomside of the unit when finished installation.
Front of view
Ceiling
Side of view
Ceiling
5~10mm
10~20mm