We recommend using the VIVO-M101(M) switchboard (for single operator installations) and
VIVO-M201(M) (for twin operator installations).
FCA2 COM FCC2
P1 P2 P3
P4 P5 P6
P15 P14 P16
ST1
FT1
ST2
FT2
FCA1
We recommend
switchboard
VIVO-D201(M).
A1
Operator 1
A2
Operator 2
G1/G4 Red cable (motor)
G2/G5 Blue cable (motor)
SW1
Main switch
• Select the number of operators using C0 (C001: one operator, C002: two operators).
• Select the directions using C1 (A1) and C2 (A2).
• Programme C7 for operation without encoder or limit switches (C700).
• For the ARES 24V operator, programme C304.
• Adjust the thrust in accordance with the weight of the gate (parameter A6).
Turning direction check: after connecting the power and activating any of the key devices, the
gate makes a reset (the display showsrS): the gate closes until it reaches the stopper, assigning this
stopper with the position "gate closed" If it opens instead of closes during the reset, change turning
direction using C1 (A1) or C2 (A2).
12
Electrical connections (except AE3324I and AE3324D)
SCA
G4
P7 P8
P11 P12
P22 P23
G7 G8
G9 G10
Courtesy
LOCK
24Vac
Lamp.
FCC1
STOP
MOTOR2 (G2-G1-COM)
Light
G4 G5 G6
Electrical connections (AE3324I and AE3324D)
ENCODER1
ENCODER2
P13 P14 P15 P16 P17 P18 P19 P20 P21 P22 P23
P1 P2 P3
P4 P5 P6
P7 P8
G5
G6
G1
G2
G3
N
L
POWER
MOTOR1 (G2-G1-COM)
VIVO-M201: 230Vac/50Hz
VIVO-M201M: 125Vac/60Hz
G1 G2 G3
P24 P25
MOTOR2
-FT
AUX
G4 G5
(Test)
24 Vdc
MOTOR1
P9 P10
P11 P12
G1 G2
A1, A2
Operators
C1, C2
Capacitors
DL4
Gate opening
DL5:
Gate closing
PUL1
Close mini-pushbutton
PUL2
Open mini-pushbutton
T
Earth connection
Operator connections A1 / A2:
G1 / G4 Open
G2 / G5 Close
G3 / G6 Common (COM), grey cable
When pressing PUL1, DL5 lights up and
the
G2/G5
and
connectors are activated.
When pressing PUL2, DL4 lights up and
the
G1/G4
and
connectors are activated.
P169V
SW1
G6
G7 G8
G9 G10
G3
G3/G6
cable
G3/G6
cable
N
L
POWER - 230V
VIVO-D201:
VIVO-D201M:
P144Y2