8. Specifications
MODEL
ENVIRONMENT
Operation Temperature
Operation Humidity
Operation Altitude
Acoustic Noise Level
MANAGEMENT
SNMP
Multi-Functional LCD
EPO (Emergency Power Off)
Volt-Free Contacts
Frequency Converter Mode
STANDARDS
Safety
EMC
Approvals
Product specifications are subject to change without further notice.
MODEL
SVT10KX
SVT20KX
SVT30KX
SVT10KX
WIRING SPEC (AWG) [MM²]
Input (Ph)
Output (Ph)
10 [5]
10 [5]
8 [8]
8 [8]
8 [8]
8 [8]
UPS BLOCK DIAGRAM
SVT20KX
0 ~ 40°C (For optimal battery life > 25°C)
<95 % and non-condensing
<1000m
Less than 65dB @ 1 Meter
Optional
Standard
Standard
Optional
Programmable
IEC/EN 62040-1
IEC/EN 62040-2 Category C3
TUV
Neutral
8 [8]
6 [13]
4 [21]
31
SVT30KX
Cable Length
Ground
10M Max
8 [8]
10M Max
6 [13]
10M Max
4 [21]