Les langues disponibles

4. Operation
Method 2:
1) If the UPS indicates a bypass abnormal error code, you cannot remove the UPS without interruption and must first power down the
load and the UPS system.
2) Make sure the bypass setting is enabled in each UPS, then turn off the running system. All UPS systems will transfer to Bypass mode.
Remove all the maintenance bypass covers and set the maintenance switches from "UPS" to "BPS". Turn off all input breakers and
battery breakers in the parallel system.
3) Turn off the output breaker and remove the parallel cable and share current cable of the UPS to be removed, then remove the unit
from the parallel system.
4) Turn on the input breaker of the remaining UPS system(s). The system(s) will transfer to Bypass mode. Set the maintenance switches
from "BPS" to "UPS" and reattach the maintenance bypass covers.
5) Turn on the remaining UPS systems.

4.6 LCD Panel Abbreviations

Abbreviation
ADD
ATO
BAT
CF
CHE
DIS
ENA
FBD
N.L
NCF
OFF
ON
OP .V
OPN
PAR
RES
RN
RS
SN
ST
SUB
TN
TR
Display content
16
Meaning
Add
Auto
Battery
Freq. Converter mode
Check
Disable
Enable
Forbidden
Neutral line loss
Normal mode (not Freq. Converter mode)
Off
On
Output voltage
Allow
Parallel, 001 means the first UPS
Reserved
First phase
First line
Second phase
Second line
Subtract
Third phase
Third line