Warning Code; Communication; Rs-232 Port; Usb Ports - Tripp-Lite SmartOnline SVT Serie Manuel Du Propriétaire

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4. Operation

4.11 Warning Code

If errors occur in the UPS but it continues to run normally, the LCD screen will show a warning. In the warning screen, the
flash. Up to 3 error codes may be displayed, each code indicating one error.
Warning code Warning event
01
Battery disconnected
02
IP neutral loss
04
IP phase abnormal
05
Bypass phase abnormal
07
Over charge
08
Low battery
09
Overload
0A
Fan failure
0B
EPO enable
0D
Over-temperature
0E
Charger failure

5. Communication

5.1 RS-232 Port

The RS-232 port is built into the UPS system's rear panel to provide communication between the UPS and computer. Use Tripp Lite's
free PowerAlert
power management software (available for download at www.tripplite.com/poweralert) to check and monitor the UPS
®
system's status via a computer. Detailed information is as follows:
1. Monitor the load level, battery status, battery voltage, UPS operation mode, input voltage, input frequency, output voltage and UPS
temperature.
2. Sets shutdown delay time.
3. Enables/disables audible alerts.
4. Supports remote shutdown.

5.2 USB Ports

A USB port is supplied on the UPS as standard.

5.3 SMART Slot

Install an optional SNMP card in this SMART slot to remotely control and monitor the UPS status via a network. You can also insert the
Relay I/O card in this slot to provide dry contact communication functions.

5.4 EPO Connector

The EPO is included as standard for site safety. Keep pins 1 and 2 closed for normal UPS operation. To enable EPO function, open
contact between pins 1 and 2.
Warning code Warning event
10
L1 IP fuse damaged
11
L2 IP fuse damaged
12
L3 IP fuse damaged
21
Line situations are different in parallel system
22
Bypass situations are different in parallel system
33
Locked in bypass after overload 3 times in
30 minutes
34
Converter current imbalanced
35
Battery fuse damaged
3A
Cover of maintenance switch is open
3C
Utility power imbalanced
3D
Bypass unstable
27
icon will