4. Operation
15: Inverter R voltage adjustment
Interface
16: Inverter S voltage adjustment
Interface
17: Inverter T voltage adjustment
Interface
18: Output R voltage calibration
Interface
19: Output S voltage calibration
Interface
20: Output T voltage calibration
Interface
Setting
Parameter 2: Choose Add or Sub to adjust inverter R voltage.
Parameter 3: The voltage range is from 0V to 9.9V. The default value is 0V.
Setting
Parameter 2: Choose Add or Sub to adjust inverter S voltage*.
Parameter 3: The voltage range is from 0V to 9.9V. The default value is 0V.
*It will display number 1 under
Setting
Parameter 2: Choose Add or Sub to adjust inverter T voltage*.
Parameter 3: The voltage range is from 0V to 9.9V. The default value is 0V.
*It will display number 2 under
Setting
Parameter 2: Shows OP.V as output voltage.
Parameter 3: Shows the internal measurement value of the output R voltage. It can be calibrated
by pressing Up or Down according to the measurement from an external voltage meter. The
calibration result will be effective upon pressing Enter. The calibration range is limited within +/-9V.
This function is normally used for parallel operation.
Setting
Parameter 2: Shows OP.V as output voltage*.
Parameter 3: Shows the internal measurement value of the output S voltage. It can be calibrated
by pressing Up or Down according to the measurement from an external voltage meter. The
calibration result will be effective upon pressing Enter. The calibration range is limited within +/-9V.
This function is normally used for parallel operation.
*It will display number 1 under
Setting
Parameter 2: Shows OP.V as output voltage.
Parameter 3: Shows the internal measurement value of the output T voltage. It can be calibrated
by pressing Up or Down according to the measurement from an external voltage meter. The
calibration result will be effective upon pressing Enter. The calibration range is limited within +/-9V.
This function is normally used for parallel operation.
*It will display number 2 under
or
to represent inverter S voltage.
or
to represent inverter T voltage.
to represent the output S voltage.
to represent the output T voltage.