Install air curtain
external wall
door frame
The installation must be positioned in such a way that the air curtain is as close as possible to
the door wall and the discharge height is as close as possible to the top of the door frame (see
drawing).
The air from the installation must be able to be blown out without hindrance, without impeding
any parts of the building, door operators, etc.
The maximum blow-out height prescribed for the model range must not be exceeded. The
model series can be found on the nameplate. This is standard inside the installation (on the
inspection hatch).
The room temperature may be a minimum of +4 °C and a maximum of +40 °C.
The discharge temperature may not exceed +55 °C.
Mounting height (maximum)
Type
Easyair S
Easyair M
Easyair L
Easyair LXX
6
revision cover
Max. mounting height
2,40 m
2,80 m
3,20 m
4,10 m
ceiling mounting kit
electric connections