Technical data

Common characteristics, all Danfoss Icon™-products
Temperature for the ball pressure test
Control polution degree
Software class
Rated impulse voltage
Operating time
Temperature range, storage and transportation
Dispossal instructions
Full data sheet available at www.danfoss.com
Radio Module & Repeater
Purpose of control
Ambient temperature range, continious use
Frequency
Transmission power
Encapsulation (IP Class)
Conformity declared acc. to following directives
Protection class
Supply voltage
App Module
Purpose of control
Ambient temperature range, continious use
Frequency
Encapsulation (IP Class)
Conformity declared acc. to following directives
Protection class
Supply voltage
Master Controller 24V and Expansion Module (optional)
Supply voltage
Supply frequency
Output voltage, actuators
Max. power consumption per actuator output
Number of actuator outputs (1 actuator per output terminal) 10 or 15 depending on type
Output voltage, thermostats
Stand-by consumption per thermostat
Max. number of thermostats
Max. length of wire from master controller to a 24 V ther-
mostat (depends on cable type used)
Stand-by consumption, Master Controller
Max. power consumption, excluding use of PWR 1 and PWR
2 outputs
Internal protection (fuse, non-replacable)
Output "Relay"
Actuator outputs, type
Output "PWR 1", type and rated max. output
Output "PWR 2", type and rated max. output
Output "PWR 3" (optional, on Expansion module – used for
dew point sensor)
Input "1" (optional, on Expansion module – use varies acc. to
application chosen)
Input "2" (optional, on Expansion module – use varies acc. to
application chosen)
Input "3", sensor input (optional, on Expansion module)
Dimensions
Conformity declared acc. to following directives
Purpose of control
Method of providing earthing
Encapsulation (IP Class)
Protection class
Ambient temperature range, continious use
Wireless Thermostat
Purpose of control
Ambient temperature range, continious use
Frequency
Transmission power
Encapsulation (IP Class)
Supply voltage
Conformity declared acc. to following directives
Protection class
24V Wired Thermostat
Purpose of control
Ambient temperature range, continious use
Encapsulation (IP Class)
Supply voltage
Conformity declared acc. to following directives
Protection class
External sensor
© Danfoss | FEC | 2020.12
Danfoss Icon™ Master Controller 24V
75 °C
Degree 2, normal household environment
Class A
4 kV
Permanently connected
-20 °C to +65 °C
The product must be disposed as electronic waste.
Transmitting and receiving device
0 °C to 40 °C
868,4–869,85 MHz
<2,5 mW
IP 20
RED, RoHS, WEEE
Radio: Class III Construction, Repeater: Class II Construction
Radio: 5 V DC, Repeater: 230 V AC 50/60 Hz
Wi-Fi transmitting and receiving device, incl. Bluetooth
0 °C to 40 °C
2,4 GHz
IP 20
RED, RoHS, WEEE
Radio: Class III
5 V DC
220-240 V AC
50/60 Hz
24 V DC
2 W
24 V DC
0,2 W
10 or 15 depending on type
If 2 × 2 × 0,6 mm² STP/UTP: 100 m
If 2 × 0,5 mm²: 150 m
If > 2 × 0,75 mm²: 200 m
< 2 W
< 50 W
2,5 A
Micro-disconnection (Type 1.B action), Max. 2 A load
Electronic disconnection (Type 1.Y action)
Micro-interruption (Type 1.C action)
Type: Permanent output, Always live 230 V, Max. 50 W
24 V DC, max. 1 W
Ext. switch input (internal 24 V pull-up)
Ext. switch input (internal 24 V pull-up)
External sensor, PT 1000 (Danfoss ESM 11)
W: 370 mm, H: 100 mm, D: 53 mm
LVD, EMC, RoHS and WEEE
Individual electronic room temperature control
Factory fitted power cord, incl. PE-conductor
IP 20
Class I
0 °C to 50 °C
Room thermostat for room temperature control
0 °C to 40 °C
869 MHz
<2,5 mW
IP 21
2 × 1,5 V AA-Alkaline batteries
RED, RoHS, WEEE
Class III
Room thermostat for room temperature control
0 °C to 40 °C
IP 21
24 V DC
EMC, RoHS, WEEE
Class III
NTC type, 47 kΩ @ 25 °C (Optional, 088U1110)
AN29434614196101-000402 | 088N2112 01 | 9