Fronius Galvo 1.5-1 208-240 Instructions De Service page 44

Masquer les pouces Voir aussi pour Galvo 1.5-1 208-240:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Fronius Galvo
Max. output fault current per
duration
Nominal output frequency
Operating frequency range
Adjustment range for mains fre-
quency
Frequency trip limit accuracy
Setting range for frequency limit
violation tolerance time
Total harmonic distortion
Power factor (cos phi)
General data
Maximum efficiency
CEC efficiency
Self-consumption at night
Self-consumption during opera-
tion
Cooling
Protection class
Dimensions h x w x d
Weight
Shipping dimensions l x h x w
Shipping weight
Permitted ambient temperature
(at 95% rel. humidity)
Permitted storage temperature
(at 95% rel. humidity)
Protection devices
Ground fault monitoring
Stand-alone operation protec-
tion
Reverse polarity protection
44
1.5-1 208-240
at 208 V
248 A/1.2 ms
at 220 V
320 A/1.1 ms
at 240 V
232 A/3.6 ms
45.0 - 65.0 Hz
45.0 - 65.0 Hz
0.016 - 600 s
0.85 - 1 ind./cap.
at 208 V
94.0%
at 220 V
94.0%
at 240 V
94.5%
at 208 V
at 220 V
at 240 V
Forced-air ventilation
24.7 x 16.9 x 8.1 in.
628 x 428 x 205 mm
30.1 x 21.7 x 11.4 in.
770 x 550 x 290 mm
-40 °F to +122 °F
-40 °C to +50 °C
-40 °F to +158 °F
-40 °C to +70 °C
Internal GFDI
(Ground Fault Detector/Inter-
2.0-1 208-240
60 Hz
0.05 Hz
5)
< 4%
1
6)
95.8%
94.5%
94.5%
94.5%
0.7 W
0.9 W
0.9 W
8.0 W
NEMA4X
36.05 lbs.
16.35 kg
43.10 lbs.
19.55 kg
rupter)
Integrated
Integrated

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Galvo 2.0-1 208-240Galvo 2.5-1 208-240Galvo 3.1-1 208-240

Table des Matières