CARLO GAVAZZI
A u t o m a t i o n C o m p o n e n t s
EXAMPLE OF ALARM PARAMETERS PROGRAMMING
P P R R O O G G R R A A M M M M I I N N G G W
It is required the disconnection of a load when a set value of absorbed
power occurs. For example when 300kW are exceeded, the alarm occurs
and the set load is disconnected.
300kW
An "UP" alarm is selected, below you'll find the recommended program-
ming:
ENABLE: YES
VARIABLES: W system (W∑)
SET POINT 1: 300kW
SET POINT 2: 295kW
295kW
ON DELAY: set the desired number of seconds: "5 seconds".
W M M 4 4 0 0 - - 9 9 6 6
17