CARLO GAVAZZI WM40-96 Manuel D'instructions page 14

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

CARLO GAVAZZI
A u t o m a t i o n C o m p o n e n t s
Page 11 (340)
NOTE
350 DIG OUT 1: This function allows to link a virtual alarm to the digital
output and to its working parameters. 351 FUNCTION: Alarm, the digital
output is enabled only if the expected alarm status occurs. Pulse, the
measured energy is retransmitted by the digital output by means of puls-
es. Remote, the digital output can be enabled through a command sent by
means of serial communication port. 352 AL LINK: select the virtual alarm
to which it has to be linked. 353 AL STATUS: "ND" (normally de-energized
relay) or "NE" (normally energized relay) 355 PULSE WEIG: selects the
pulse weight (kWh per pulse). 356 OUT TEST: enables the TEST (YES), dis-
ables the TEST (NO). 357 POWER TEST: sets the simulated power value
(kW) to which a proportional pulse sequence according to "PULSE WEIG"
corresponds. The function is active until you remain within the menu and
it is used when the output is connected to a PLC.
440 TARIFF: it allows to select the tariffs mode.
450 DIG IN 1: it allows to set the digital inputs parametres. 451 FUNCTION:
P P R R O O G G R R A A M M M M I I N N G G W
List of available
variables
As DIG OUT 1
As DIG IN 6
function type selection. 452 PULSE TYPE: it allows to set the pulse type.
453 PULSE WEIG: it allows to set the pulse weight.
470 AN OUT 1: this submenu allows the programming of the analogue
outputs (0-20mA, 0-10V). 471 VARIABLES: select the variable to be
retransmitted by means of the analog output. 472 MIN INPUT: minimum
value of the variable input range to which the "MIN OUTPUT" value,
retransmitted by the analogue output, will be linked. 473 MAX INPUT:
maximum value of the variable input range to which the "MAX OUTPUT"
value, retransmitted by the analogue output, will be linked. 474 MIN OUT-
PUT: set the value expressed as % of the output range (0-20mA, 0-10V) to
be linked to the minimum measured value. 475 MAX OUTPUT: select the
value expressed as % of the output range (0-20mA, 0-10V) to be linked to
the maximum measured value.
520 PROCESS: it allows to set the process signal parameters. 521 UNIT:
engineering unit selection (°C or °F). 522 PROBE: probe selection. 523
W M M 4 4 0 0 - - 9 9 6 6
As AN OUT 4
Page13 (530)
List of available variables
MIN ELECT: selection of electrical scale minimum value. 524 MAX ELECT:
selection of electrical scale maximum value
525 MIN DISPLAY: selection of the displayed minimum value. 526 MAX
DISPLAY: selection of the displayed maximum value.
Some specific menus display only if the relevant modules are
installed.
13
Key-pad
Push for at
least 2 s

Publicité

Table des Matières
loading

Table des Matières