Drain Piping Work; Electrical Wiring; Power Supply Wiring; Connecting Remote Controller, Indoor And Outdoor Transmission Cables - Mitsubishi Electric CITY MULTI PFD-P250VM-E Manuel D'installation

Indoor unit
Masquer les pouces Voir aussi pour CITY MULTI PFD-P250VM-E:
Table des Matières

Publicité

Caution:
Use refrigerant piping made of phosphorus deoxidized copper and cop-
per alloy seamless pipes and tubes". In addition, be sure that the inner
and outer surfaces of the pipes are clean and free of hazardous sulphur,
oxides, dust/dirt, shaving particles, oils, moisture, or any other contami-
nant.
Never use existing refrigerant piping.
- The large amount of chlorine in conventional refrigerant and refrigerator oil
in the existing piping will cause the new refrigerant to deteriorate.
Store the piping to be used during installation indoors and keep both
ends of the piping sealed until just before brazing.
- If dust, dirt, or water gets into the refrigerant cycle, the oil will deteriorate and
the compressor may fail.
[Fig. 6.1.1] (P.3)
A Piping on site
Expand the end of the pipe and braze it to the connecting pipe (non-oxidizing
brazing).
B Piping on site
Expand the end of the pipe and braze it to the connecting pipe (non-oxidizing
brazing).
[Fig. 6.1.2] (P.3)
A Pipe cover
C Refrigerant piping (gas)

6.2. Drain piping work

[Fig. 6.2.1] (P.3)
A Drain pan
C As seen from front of unit
E Emergency drain piping on site
G Drain piping on site (for humid filter)

7. Electrical wiring

Precautions on electrical wiring
Warning:
Electrical work should be done by qualified electrical engineers in accord-
ance with "Engineering Standards For Electrical Installation" and supplied
installation manuals. Special circuits should also be used. If the power cir-
cuit lacks capacity or has an installation failure, it may cause a risk of elec-
tric shock or fire.
1. Be sure to take power from the special branch circuit.
2. Be sure to install an earth leakage breaker to the power.
3. Install the unit to prevent that any of the control circuit cables (remote control-
ler, transmission cables) is brought in direct contact with the power cable out-
side the unit.
4. Ensure that there is no slack on all wire connections.
5. Some cables (power, remote controller, transmission cables) above the ceiling
may be bitten by mouses. Use as many metal pipes as possible to insert the
cables into them for protection.
6. Never connect the power cable to leads for the transmission cables. Otherwise
the cables would be broken.
7. Be sure to connect control cables to the indoor unit, remote controller, and the
outdoor unit.
8. Put the unit to the ground on the outdoor unit side.
9. Select control cables from the conditions given in below.
Caution:
Be sure to put the unit to the ground on the outdoor unit side. Do not con-
nect the earth cable to any gas pipe, water pipe, lightening rod, or telephone
earth cable. Incomplete grounding may cause a risk of electric shock.
Types of control cables
1. Wiring transmission cables
Types of transmission cables
Shielding wire (2-core)
CVVS, CPEVS or MVVS <max length: 200 m>.
Cable diameter
2
More than 1.25 mm
2. Remote controller cables
Types of cables
2-core cable (unshielded)
Cable diameter
0.3 to 1.25 mm
Length
Less than 200 m
12
B Pipe mounting plate
D Refrigerant piping (liquid)
B Drain hose
D Main drain piping on site
F Trap (on-site piping work)
MA remote controller
2
1. Ensure that the drain piping is downward (pitch of more than 1/100) to the
outdoor (discharge) side. Do not provide any trap or irregularity on the way.
2. Ensure that any cross-wise drain piping is less than 20 m (excluding the differ-
ence of elevation). If the drain piping is long, provide metal braces to prevent it
from waving. Never provide any air vent pipe. Otherwise drain may be ejected.
3. Do not provide any odor trap at the drain discharge port.
4. Put the end of the drain piping in a position where no odor is generated.
5. Do not put the end of the drain piping in any drain where ionic gases are
generated.
6. Check drainage by pouring water into the drain pan and check to see that it
drains properly.
7. Check for ease of operation of the fault detection float switch in the drain pan,
and breakage of leads.
8. Provide a drain trap to the drain piping installed on site.
* The loop on the drain hose provided with the unit does not function as a trap; it
is only used to drain water to the main drain pan at the bottom of the product.
Note:
If the rise portion is long, there will be a lot of returned water in an operation
stop, generating slime or odor during off-season. Ensure that the rise por-
tion is at a minimum.
Caution:
Always prepare the water seal by filling the trap with water from the drain
pan during test operation. Inject water into the drain trap during the periodic
check (six-monthly) to check water-sealing. If the trap is not filled with water,
it will cease to function and this may result in leaks.
Caution:
Pipe the drain piping to ensure that it discharges drain, and insulate it to
prevent dew condensation. A failure to the piping work may cause water
leakage and so wet your property.

7.1. Power supply wiring

Model
Power supply
Power supply wiring cross-section
Earth wiring cross-section
Earth leakage
Type <capacity>
breaker
Rated sensitivity
Wiring breaker (NFB)
Note:
1. Bear in mind ambient conditions (ambient temperature,direct sunlight,
rain water,etc.) when proceeding with the wiring and connections.
2. The wire size is the minimum value for metal conduit wiring. The power
cord size should be 1 rank thicker consideration of voltage drops.
Make sure the power-supply voltage does not drop more than 10 %.
3. Specific wiring requirements should adhere to the wiring regulations of
the region.
4. Wiring cross-sections noted are the minimum values for metal and plas-
tic wiring conduits (containing up to three cables).
Power supply cords of appliances shall not be lighter than design 245 IEC 53
or 227 IEC 53.
A switch with at least 3 mm contact separation in each pole shall be provided
by the Air conditioner installation.
Caution:
1. Use only breakers and fuses of the correct capacity. Use of larger capac-
ity fuses, or wire may result in a fault and smoke or flames.
2. Wire the power supply so that no tension is imparted. Otherwise discon-
nection, heating or fire result.
7.2. Connecting remote controller, indoor
and outdoor transmission cables
Connect indoor unit TB5 and outdoor unit TB3. (Non-polarized 2-wire)
The "S" on indoor unit TB5 is a shielding wire connection. For specifications
about the connecting cables, refer to the outdoor unit installation manual.
Do not connect the indoor unit terminal block (TB5) to another indoor unit ter-
minal block (TB5) that is connected to a different outdoor unit.
Connect terminals M1 and M2 of the terminal block for indoor-outdoor trans-
mission line (TB3) on the outdoor unit to their respective terminals M1 and M2
of the terminal block for indoor-outdoor transmission line (TB5) on the indoor
unit. * Only use shielded cables.
Connect one end of the grounding wire of the shielded cable to the earth screw
of the OC and the other end to the S terminal of terminal block (TB5) on the
indoor unit.
PFD-P250VM-E
PFD-P500VM-E
380 - 415V
2
2
2.5 mm
4.0 mm
2.5 mm
2
4.0 mm
2
20 A
30 A
30 mA less than 0.1 s
20 A
30 A

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

City multi pfd-p500vm-e

Table des Matières