Approved ET 200eco PN distributed I/O devices
You can find the EU prototype test certificate with the approved ET 200eco PN I/O devices on the Internet at the following
link: Service & Support (http://support.automation.siemens.com/WW/view/en/71748103)
Table 1
Approved ET 200eco PN distributed I/O devices
Designation
Digital input devices
8 DI DC 24V 4×M12
8 DI DC 24V 8×M12
16 DI DC 24V 8×M12
Digital output devices
8 DO DC 24V/1,3A 4×M12
8 DO DC 24V/0,5A 4×M12
8 DO DC 24V/1,3A 8×M12
8 DO DC 24V/2,0A 8×M12
16 DO DC 24V/1,3A 8×M12
Digital input/digital output device
8 DIO DC 24V/1,3A 8×M12
Analog input device
8 AI 4 U/I + 4 RTD/TC 8×M12
8 AI RTD/TC 8×M12
Analog output device
4 AO U/I 4×M12
IO-Link master
4 IO-L + 8 DI + 4 DO DC 24V/1,3A 8×M12
4 IO-L 4×M12
Approval
ATEX approval
According to EN 60079-15 (Electrical apparatus for potentially explosive atmospheres - Part 15: Type of protection "n"),
EN 60079-0 (Electrical apparatus for potentially explosive gas atmospheres - Part 0: General Requirements) and EN 60079-31
(Equipment dust ignition protection by enclosure "t").
II 3 G Ex nA IIC T4 Gc
II 3 D Ex tc IIIC T90°C Dc
DEKRA 12ATEX0220 X
OR
According to EN IEC 60079-7 (Electrical apparatus for potentially explosive atmospheres - Part 7: Increased safety "e"),
EN IEC 60079-0 (Electrical apparatus for potentially explosive gas atmospheres - Part 0: General Requirements) and
EN 60079-31 (Electrical apparatus for potentially explosive atmospheres – Part 31: dust ignition protection by enclosure "t").
II 3 G Ex ec IIC T4 Gc
II 3 D Ex tc IIIC T90°C Dc
DEKRA 20ATEX0119 X
Use of the ET 200eco PN in zone 2/zone 22 hazardous areas
A5E03879075-AC, 12/2021
Article number
6ES7141-6BF00-0AB0
6ES7141-6BG00-0AB0
6ES7141-6BH00-0AB0
6ES7142-6BF00-0AB0
6ES7142-6BF50-0AB0
6ES7142-6BG00-0AB0
6ES7142-6BR00-0AB0
6ES7142-6BH00-0AB0
6ES7147-6BG00-0AB0
6ES7144-6KD00-0AB0
6ES7144-6KD50-0AB0
6ES7145-6HD00-0AB0
6ES7148-6JA00-0AB0
6ES7148-6JD00-0AB0
9