GB
A
PICTURES
[1] KNX 4 AC Motor Controller WM 100-120 V AC,
wall mounted version
B
MOUNTING
[1] Choose the optimal location: flat and large surface
[2] Mount the 4 AC Motor Controller WM
[3] Connect power supply and wiring to the
Motor Controller
C
WIRING
[1] Tool for all terminals
[2] Wiring diagram
[3] Check the correct running directions of the end product
UP: the end product goes up ( C + s)
STOP: the end product stops ( C + t+ s)
DOWN: the end product goes down ( C + t)
To close window press UP, to open window press
DOWN.
[4] Possible switches
1.
Inteo Centralis IB, Ref. 1810138
2.
Double push button
D
CONFIGURATION
[1] Reset / Prog button
With this button, you can access the basic configura-
tion of the Motor Controller.
The „US" LED is steadily blinking when the mains (110 V)
and the KNX bus power are actively connected to the
device. The device is ready for operation when the „US" LED
is blinking. The Reset / Prog button can be used to select a
switch ergonomic when the device is in default condition
and is not programmed by the ETS Software. The different
ergonomics are described in the user manual.
CABLE
Connection to ...
Motors
Switches
Group control
KNX bus
100 - 120 V AC
Cables
Min.: 4 x 0.75 mm
/19 AWG
2
Max.: 4 x 2.5 mm
/14 AWG
2
Min.: 3 x 0.6 mm/22 AWG
Max.: 3 x 2.5 mm
/14 AWG
2
Min.: 3 x 0.6 mm/22 AWG
Max.: 3 x 1.5 mm
/16 AWG
2
2 x 0.8 mm/20 AWG
Min.: 3 x 1.5 mm
/16 AWG
2
Max.: 3 x 2.5 mm
/13 AWG
2
[2] Selection of switch ergonomic
Local push button ergonomics and the type of end
products to be preselected:
• Screen mode
• Venetian blind, European mode
• Venetian blind, US mode
The default mode is: Venetian blind, EU mode.
1.
To toggle between modes, press shortly the
Reset / Prog button. Repeat until the LED, accord-
ing to the desired configuration, lights up.
[3] Factory RESET
[4] Learn running and tilting times/
length
1.
Press immediately when lower end limit
is reached
2.
Maintain stop for duration of tilting
[5] Symbols: actions
1.
Up
2.
Stop
[6] Symbols: end product status
1.
Up
2.
High position
3.
Down
4.
Low position
When electronic motors are to be controlled through this
Motor Controller device it is mandatory to configure the start-
up delay time for electronic motors in the Motor Controller
settings. To configure the start-up delay time WT Setting Tool
Ref. 1811242 can be used.
Twisted pairs
-
Recommended
Recommended
Required, following KNX
topology guidelines
-
animeo KNX 4 AC MOTOR CONTROLLER . REF. 5110785 B -
Max. distance
150 m
100 m
50 m