SINEAX TV829 Art.-no. 158 320 and 158 338
Specifications (continued)
Transmission behavior
Gain error
Cutoff frequency (-3 dB)
Temperature influence
Power supply
Power supply
Isolation
Galvanic isolation
Test voltage
Working voltage
(basic insulation) to
EN 61010-1
Rated insulation voltage
to EN 50124-1
48
48
48
48
< 0,3 % meas.val.
> 5 kHz
1)
100 ppm/K full scale
20 ... 253 V AC/DC
AC 48 ... 62 Hz, approx. 2 VA; DC approx. 1 W
3-port isolation between input, output, and power supply
10 kV AC input against output and power supply
4 kV AC output against power supply
Up to 2200 V AC/DC across input, output, and
power supply with overvoltage category III
and pollution degree 2
(transient overvoltage: max. 13.5 kV).
Up to 2200 V AC/DC across input, output, and
power supply with overvoltage category III
and pollution degree 2