2.3 SINEAX TV829 Art.-no. 158 320 and 158 338
Rating plate, range selection
The high voltage isolators of the SINEAX TV829 Series must be installed
only by qualified and specially trained personnel authorized by the
operating company. Be sure that there is sufficient spacing or isolation
from neighboring devices and protection against electrical shocks! Do not
connect the device to power supply before it is professionally installed!
Caution!
Do not change the measurement range during operation! The ranges are
selected by turning an insulated rotary coding switch on the device front
using a screw driver.
2.4 SINEAX TV829 Art.-no. 158 320 and 158 338:
Conductor cross sections
Max.:
each 1 x 2.5 mm
each 1 x 4 mm
each 2 x 1.5 mm
each 2 x 2.5 mm
Min.:
each 1x 0.5 mm
Stripping length of conductors or sleeve length: 8 mm
44
44
44
44
2
stranded wire with sleeve
2
solid
2
stranded wire with sleeve
2
solid
2
solid or stranded wire with sleeve