System 3 settings and statistics menu
User code for menu access: 0322
Factory
Area
setting
System
1
1, 2, 3, 4
TSet
40 °C
15 °C ... 90 °C
TFcalculated Yes
Yes, No
TMin
No
Yes, No
TMin
25 °C
15 °C ... 60 °C
TMax
Yes
Yes, No
TMax
50 °C
30 °C ... 90 °C
t.hold
5 min
1 ... 30 min
Cooling
No
Yes, No
TCool
16 °C
5 °C ... 25 °C
TMin
No
Yes, No
TMin
10 °C
5 °C ... 20 °C
RH% control Yes
Yes, No
Chiller option No
Yes, No
Vmin
0,0 V
0,0 ... 9,9 V
Vmax
10,0 V
0,1 ... 10,0 V
Increment
0,1V
0,1 ... 1,0 V
tPlay
0,2 V
0,0 ... 1,0 V
Feedback
No
Yes, No
Block. prot.
Yes
Yes, No
PWM
Heating Heating, Solar
Slab drying
-
-
TStart
20 °C
10 °C ... 30 °C
TMax
45 °C
20 °C ... 60 °C
Rise
5 K
1 ... 10 K
Rise time
24 hours 1 ... 24 h
tBacking
7 days
1 ... 20 d
Start
-
Start, Cancel
12
Meaning
System selection
Nominal flow temperature
Option to recalculate the flow tem-
perature from the return temperature
confirmed
Minimum temperature option for the
heating circuit
Minimum temperature of the heating
circuit
Maximum temperature option for the
heating circuit
Maximum temperature of the heating
circuit
Time for which a calculated flow tem-
perature is applied
Cooling option
Cooling temperature
Minimum cooling temperature option
Minimum cooling temperature
Dew point detector option (TPS)
Cooling request option on
Minimum control signal
Maximum control signal
Control signal increment/decrement
Control signal increment/decrement for
a direction change
Feedback signal option
Anti-seizing option
PWM A Curve
Slab drying submenu
Slab drying start temperature
Slab drying hold temperature
Slab drying rise value
Slab drying rise time
Slab drying hold time
Slab drying activation/deactivation
Factory
Area
setting
Language
Italiano
Deutsch, Eng-
lish, Français,
Italiano,
Español, Portu-
guês, 中文
Reset
No
Yes, No
Operation
-
0 ... 9999
Pump
-
0 ... 9999
Backup heat. -
0 ... 9999
S1 value
-
max. 999,9 °C
S2 value
-
max. 999,9 °C
S3 value
-
max. 999,9 °C
Version
-
-
All relays
Auto
Auto, Off
Man 1
Auto
On, Auto, Off
Man 2.3
Auto
Mixer Close,
Auto, Mixer
Open, Off
Man 4
Auto
On, Auto, Off
Back
Meaning
Language selection
Reset to factory settings
Operating days of the controller (bal-
ance, the value cannot be reset)
Statistics, these values cannot be reset
(see page 20)
Software version display
Select operating mode of all relays
Relay 1 in manual mode
Relay 2.3 in manual mode
Relay 4 in manual mode