Factory
Area
setting
TMax
50 °C
30 °C ... 90 °C Maximum temperature of the heating
Remote regu-
No
Yes, No
lation
Cooling
No
Yes, No
TCool
16 °C
5 °C ... 25 °C Cooling temperature
TMin
No
Yes, No
TMin
10 °C
5 °C ... 20 °C Minimum cooling temperature
RH% control
Yes
Yes, No
Chiller option No
Yes, No
VMin
0,0 V
0,0 ... 9,9 V
VMax
10,0 V
0,1 ... 10,0 V Maximum control signal
Increment
0,1V
0,1 ... 1,0 V
tPlay
0,2 V
0,0 ... 1,0 V
Feedback
No
Yes, No
Block. prot.
Yes
Yes, No
PWM
Heating Heating, Solar PWM A Curve
Slab drying
-
-
TStart
20 °C
10 °C ... 30 °C Slab drying start temperature
TMax
45 °C
20 °C ... 60 °C Slab drying hold temperature
Rise
5 K
1 ... 10 K
Rise time
24 hours 1 ... 24 h
tBacking
7 days
1 ... 20 d
Start
-
Start, Cancel Slab drying activation/deactivation
Language
Italiano
Deutsch, Eng-
lish, Français,
Italiano,
Español, Por-
tuguês, 中文
Reset
No
Yes, No
Operation
0
0 ... 9999
14
Meaning
circuit
Remote control option
Cooling option
Minimum temperature option
Dew point detector option (TPS)
Cooling request option on
Minimum control signal
Control signal increment/decrement
Control signal increment/decrement
for a direction change
Feedback signal option
Anti-seizing option
Slab drying submenu
Slab drying rise value
Slab drying rise time
Slab drying hold time
Language selection
Reset to factory settings
Operating days of the controller (bal-
ance, the value cannot be reset)
Factory
Area
setting
Pump
-
0 ... 9999
Backup heat. -
0 ... 9999
S1 value
-
max. 999,9
°C
S2 value
-
max. 999,9
°C
S3 value
-
max. 999,9
°C
Version
-
-
All relays
Auto
Auto, Off
Man 1
Auto
On, Auto, Off
Man 2.3
Auto
Mixer Close,
Auto, Mixer
Open, Off
Man 4
Auto
On, Auto, Off
Back
5
Indications, functions and options
Note
The displayed channels, parameters and setting ranges depend on
the chosen system, the selected functions and options, and the com-
ponents connected to the system.
5.1 Home screen
The home screen is a graphical representation of the current system status.
The following settings are available:
Standby
The room thermostat does not request heating nor cooling.
Meaning
Statistics, these values cannot be
reset (see page 20)
Software version display
Select operating mode of all relays
Relay 1 in manual mode
Relay 2.3 in manual mode
Relay 4 in manual mode