Code
Definition
19
Electrical Grounding
Outgoing Water
32
Temperature Sensor
Heat Exchanger Outgoing
33
Temperature Sensor
Combustion Air
34
Temperature Sensor Fault
Outside temperature
41
thermistor
Inlet water temperature
51
thermistor
Modulating Solenoid Valve
52
Signal
61
Combustion Fan
65
Water Flow Control
70
PC Board
71
Solenoid Valve Circuit
72
Flame Sensing Device
79
Water Leak Detected
LC #
Scale Build-up in Heat
(LC0,
Exchanger (when checking
LC1,
maintenance code history,
LC2,...)
"00" is substituted for "LC")
Maintenance has been
FF
performed
No
Nothing happens when
code
water flow is activated.
Remedy
Check all components for electrical short.
Check sensor wiring for damage.
Measure resistance of sensor.
Clean sensor of scale build-up.
Replace sensor.
Check for restrictions in air flow around unit and vent terminal.
Check sensor wiring for damage.
Measure resistance of sensor.
Clean sensor of scale build-up.
Ensure fan blade is tight on motor shaft and is in good condition.
Replace sensor.
Check sensor wiring for damage.
Measure resistance of sensor.
Clean sensor of scale build-up.
Replace sensor.
licensed
Check modulating gas solenoid valve wiring harness for loose or damaged terminals.
professional
Measure resistance of valve coil.
only
Ensure fan will turn freely.
Check wiring harness to motor for damaged and/or loose connections.
Measure resistance of motor winding.
The water flow control valve has failed to close during the bath fill function. Immediately turn
off the water and discontinue the bath fill function. Contact a licensed professional to service
the appliance.
Check PC board DIP switches for correct position.
Check the connection harness at the connection on the PC board.
Replace PC board.
Replace the PC Board.
Verify flame rod is touching flame when unit fires.
Check all wiring to flame rod.
Remove flame rod and check for carbon build-up; clean with sand paper.
Check inside burner chamber for any foreign material blocking flame at flame rod.
Measure micro amp output of sensor circuit with flame present.
Replace flame rod.
Water has been detected at the bottom of the unit. Turn off water supply. Check all plumbing
internally for leakage.
LC0~LC9 indicates that there is scale build up in the heat exchanger and that the heat
exchanger needs to be flushed to prevent damage. Refer to the flushing instructions in the
manual. Hard water must be treated to prevent scale build up or damage to the heat
exchanger.
To operate the water heater temporarily until the heat exchanger can be flushed, push the
On/Off button on the temperature controller 5 times. Repeated LC codes will eventually
lockout the water heater.
Please call Rinnai technical department.
Indicates a licensed professional performed maintenance or corrected an issue.
Clean inlet water supply filter.
On new installations ensure hot and cold water lines are not reversed.
Verify you have at least the minimum flow rate required to fire unit.
Check for cold to hot cross over. Isolate circulating system if present. Turn off cold water to
the unit, open pressure relief valve; if water continues to flow, there is bleed over in your
plumbing.
licensed
Verify turbine spins freely.
professional
Measure the resistance of the water flow control sensor.
only
If the display is blank and clicking is coming from the unit, disconnect the water flow servo
motor (GY, BR, O, W, P, BL, R). If the display comes on then replace the water flow servo
motor.
Value Series Manual
35