Guide de programmation du FC 300
35-27 Term. X48/7 High Temp. Limit
Range:
Application
[Application dependant]
dependent*
3.21.4 35-3* Entrée temp. X48/10 (MCB 114)
35-34 Term. X48/10 Filter Time Constant
Range:
0.001 s*
[0.001 - 10.000 s]
35-35 Term. X48/10 Temp. Monitor
Ce par. permet d'activer ou désactiver la surveillance de température pour la borne X48/10. Les limites de temp. sont définies aux par. 35-36/37.
Option:
[0] *
Désactivé
[1]
Activé
35-36 Term. X48/10 Low Temp. Limit
Range:
Application
[Application dependant]
dependent*
35-37 Term. X48/10 High Temp. Limit
Range:
Application
[Application dependant]
dependent*
3.21.5 35-4* Entrée ANA X48/2 (MCB 114)
35-42 Term. X48/2 Low Current
Range:
4.00 mA*
[Application dependant]
35-43 Term. X48/2 High Current
Range:
20.00 mA*
[Application dependant]
35-44 Term. X48/2 Low Ref./Feedb. Value
Range:
0.000*
[-999999.999 - 999999.999 ]
35-45 Term. X48/2 High Ref./Feedb. Value
Range:
100.000*
[-999999.999 - 999999.999 ]
Fonction:
Fonction:
Entrer constante de tps du filtre. (constante de tps numérique du filtre passe-bas de 1er ordre pour
suppression du bruit électrique sur la borne X48/10). Une valeur élevée améliore l'atténuation mais
accroît le retard via le filtre.
Fonction:
Fonction:
Fonction:
Fonction:
Saisir le courant (mA) correspondant à la valeur de référence basse (définie au par. 35-44). La valeur
doit être réglée sur > 2 mA afin d'activer la fonction de temporisation au par. 6-01.
Fonction:
Saisir le courant (mA) correspondant à la valeur de référence haute (définie au par. 35-45).
Fonction:
Saisir valeur de référence ou de signal de retour (en tr/min, Hz, bar, etc.) correspondant à la tension
ou au courant défini au par. 35-42.
Fonction:
Saisir valeur de référence ou de signal de retour (en tr/min, Hz, bar, etc.) correspondant à la tension
ou au courant défini au par. 35-43.
MG.33.M8.04 - VLT® est une marque déposée Danfoss
3 Description des paramètres
3
235