General Technical Specifications - Rittal 7979.711 Notice D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Mass configuration / initial commissioning, Technical specifications
Note:
EN
Once a slave RCM has paired with a master RCM, it can no longer be paired with a dif-
ferent master RCM. To do so, you will need to reconfigure the slave RCM via the PDU
Mode menu. The display will show "PDU", which also applies to the RCM in this instance.
Note:
Software updates for the slave RCM are distributed via the master RCM. The master RCM
must be updated first. For further information, please visit www.rittal.com or contact Rittal
Service (see section 10). The software updates are subsequently distributed automatical-
ly among the individual slave RCMs.
8
Mass configuration / initial commissioning
To allow easy and quick commissioning of several RCMs, they can be preconfigured using a special
configuration file. The configuration file copied to a USB data carrier allows several RCMs to be config-
ured in just a few minutes without an operational network connection being required. To edit the file on
a PC, you will need either the RCM serial numbers or the first MAC address of the RCM network inter-
faces. A predefined sample file as well as a description of the procedure can be found on the PDU prod-
uct pages at our website.
9
Technical specifications
9.1

General technical specifications

Technical specifications
Temperature application range:
Humidity application range:
Protection category:
Protection class:
Overvoltage category:
Degree of contamination:
max. operating height:
min. operating time:
EU conformity:
Input voltage range (L – N)
Input current
No. of phases
Differential current measurement range AC/DC
Connection cable type
No. of wires
32
Temperature Operation: +5 °C...+50 °C (at 100% load))
Temperature Storage: -20 °C...+70 °C
10%...95% relative humidity, non-condensing
IP 20 to IEC 60 529
1
II
2
3,000 meters above sea level
100,000 h
Low-Voltage Directive 2014/35/EU
EMC Directive 2014/30/EU
IEC/EN 62368
90 V...260 (400) V AC, 50...60 Hz
16 A/32 A (depending on variant)
1 or 3 depending on RCM variant
+/- 100 mA
H05-VV
3/5 (single-phase/3-phase RCM)
Rittal RCM Inline Meter

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

7979.7127979.7137979.714

Table des Matières