PROGRAMMING OF RELAY OUTPUTS
In addition to the "dedicated relay" status outputs, such as automatic disabled, failure to
start, pump running, controller fault, fuel reserve, etc..., and "alarm summary relay" (see
electrical panel wiring diagram), two status relay outputs "OUT AUX 1, OUT AUX 2" are
available for programmed inputs "IN AUX1, IN AUX2, IN AUX3".
FUNCTION
Operating Mode
"Oper. Mode
OUT AUX1"
Operating Mode
"Oper. Mode
OUT AUX2"
IMPORTANT:
- The relay activates, closes the contact, when an alarm condition occurs.
SELECTABLE
DEFAULT
FIELDS
SETTINGS
000/016
000/016
000 = Disabled
001 = IN AUX 1 input alarm
002 = IN AUX 2 input alarm
003 = IN AUX 3 input alarm
004 = Heater / Battery charger alarm
005 = Remote start command
015
006 = Low engine oil pressure alarm
007 = High engine temperature alarm
008 = Panel supply voltage failure alarm
009 = Low battery voltage alarm
010 = Engine rpm alarm
015 = Pump pressure alarm
016 = Pump running
000 = Disabled
001 = IN AUX 1 input alarm
002 = IN AUX 2 input alarm
003 = IN AUX 3 input alarm
004 = Heater / Battery charger alarm
005 = Remote start command
000
006 = Low engine oil pressure alarm
007 = High engine temperature alarm
008 = Panel supply voltage failure alarm
009 = Low battery voltage alarm
010 = Engine rpm alarm
015 = Pump pressure alarm
016 = Pump running
39