3.2 Preparation of the mounting – countersunk mounting
In order to countersink the control in the wall, a cutout is necessary
Dimensions of cutout: 160mm x 102mm
Installation depth: 39.5mm
See also technical data
Ensure suffi cient back ventilation of the control unit.
3.3 Preparation of the electrical connection – open housing
Work on the casing may only be performed with a normal screwdriver. Using a cordless screwdriver may
cause irreparable damage to the housing.
Remove the four housing screws 1
Pull the lid 2 from the control unit.
Loosen the clamps 3
WE DO IT FIRST.
Instructions for installation and use – only for experts
max. R5mm
Fig. 3 Wall cutout
1
Fig.4 Remove lid
P. 5/14
2
3
EN