IONISATION CURRENT MEASUREMENT
The current minimum for the working
equipment is 1.4 µA. The burner gi-
ves a clearly greater current which
will not normally require any controls.
If, however, you wish to measure the
ionisation current, you have to connect
a milliammeter in series with the ioni-
sation electrode cable as shown in the
diagram
ELECTRODES/IONISATION PROBE ADJUSTMENT DIAGRAM
Model
TBG 50LX PN ME
TBG 80LX PN ME
TBG 110LX PN ME
TBG 140LX PN ME
A
B
C
5
3
3
5
8
5
5
5
5
38 / 69
0006081046 - ed 2006/09
N°0002935020
N°0002935020
REV.: 04/09/06
REV.: 04/09/06
Legend:
1- Ionisation electrode
2- Ignition electrode
3- Defl ector disk
4- Mixer
5- Gas outlet pipe