Problem - Cause - Solution - baltur TBG 50LX PN ME Mode D'emploi

Masquer les pouces Voir aussi pour TBG 50LX PN ME:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

DETAILS OF PROBLEM
The apparatus goes into "lock-out" with
the fl ame (red light on).
Fault restricted to fl ame control device.
The apparatus goes into "lock-out", gas
fl ows out, but there is no fl ame (red light
on).Fault restricted to ignition circuit.
The apparatus goes into "lock-out", gas
fl ows out, but there is no fl ame (red light
on).
TWO-STAGE GAS BURNERS: TROUBLE-SHOOTING GUIDE
POSSIBLE CAUSE
1) Disturbance to ionization current from
ignition transformer.
2)
Flame sensor (ionization probe) ineffi -
cient.
3) Flame sensor (ionization probe) position
incorrect.
4) Ionization probe or relative earth cable.
5) Electrical connection cut-off by fl ame sen-
sor.
6) Ineffi cient draught or fumes passage bloc-
ked.
7) Flame disk or combustion heads dirty or
worn.
8) Equipment fault.
9) No ionization.
1) Fault in ignition circuit.
2) Ignition transformer cable discharges to
earth.
3) Ignition transformer cable disconnected.
4) Ignition transformer faulty.
5) The distance between electrode and earth
is incorrect.
6) Isolator dirty, so electrode discharges to
earth.
1) air/gas ratio incorrect.
2) Gas pipe has not been properly bled of air
(in the case of fi rst ignition).
3) The gas pressure is insuffi cient or exces-
sive.
4) Air fl ow between disk and head too nar-
row.
41 / 69
0006081046 - ed 2006/09
SOLUTION
1) Invert the ignition transformer power
supply (230V side) and check using an
analog micro-ammeter.
2) Replace fl ame sensor.
3) Correct the position of the fl ame sensor,
and then check its effi ciency by inserting
the analog micro-ammeter.
4) Check visually and using the instrument.
5) Restore the connection.
6) Ensure that the boiler fumes passage and
chimney connection are free.
7) Visually check and replace, if necessary.
8) Replace.
9) If the "earth" of the apparatus is not effi -
cient, do not check the ionization current.
Check the effi ciency of the "earth" at the
terminal concerned of the apparatus and
at the "earth" connection of the electric
system.
1) Check the ignition transformer power
supply (230V) and high voltage circuit
(electrode to earth or isolator broken
under locking terminal).
2) Replace.
3) Connect.
4) Replace.
5) Position at the correct distance.
6) Clean or replace isolator and electrode.
1) Correct the air/gas ratio (there is probably
too much air or very little gas).
2) Bleed the gas pipe again, taking great
care.
3) Check the maximum gas pressure value
at the time of ignition (use a water pres-
sure gauge, if possible).
4) Adjust the disk/head opening.