Commissioning
®
Availability in ReadWin
2000, HART
DISPLAY
Activating the values to be shown on the device display:
• Display: PV (= Primary Value)
• Display: sensor value
• Display: RJ value
• Display Analogue output value
• Display: Status
• Display: percentage value (on/off)
The primary value (PV) is displayed as a
percentage.
!
Note!
In order to activate the values to be shown in the device display using HART
module DXR 375: Add (DXR=x) of the values to be displayed and enter the sum.
• Display: time (2s, 4s, 6s, 8s)
• Display: figures after decimal point (0,1,2)
• Display PV text (customer specific text, 8 characters)
®
Availability in ReadWin
2000, HART
Diagnostics
Display of information required for device diagnostics.
• Device status or error code
(See chapter 9.2 "Error messages")
• Last error code (status) or previous error code
(See chapter 9.2 "Error messages")
• Status sensor (0 = no error; 0 ≠ error)
• Configuration changed
Diagnostics
• Static revision
The "Static revision" is increased on every parameter change. This is for compliance to
21 CFR Part 11, showing that no further parameter changes have been made.
• Sensor max. value
• Sensor min. value
• RJ max. value
• RJ min. value
Display of the maximum process value. The process value will be accepted after starting
the measurement.
Display of the minimum process value. The process value will be accepted after starting
the measurement.
Display of the maximum and minimum measured temperatures of the internal Pt100 DIN
B comparison measurement point.
!
Maximum process value is changed to the actual process value on write access. On reset
to factory default value the default value is entered -9999.99.
Minimum process value is changed to the actual process value on write access. On reset
to factory default value the default value is entered +9999.99.
68
Function group DISPLAY
®
handheld terminal DXR 375 (symbol
Function group DIAGNOSTICS
®
handheld terminal DXR 375 (symbol
Note!
7
)
(DXR=1)
(DXR=2)
(DXR=8)
(DXR=16)
(DXR=32)
off (DXR=0)
on (DXR=64)
®
handheld
7
)
7
®
ReadWin
2000
/FieldCare
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
7
®
ReadWin
2000
/FieldCare
+
+
+
+
-
+
+
+
-
-
+
+
+
+
+
+
+
+
Endress+Hauser
TMT142