Commissioning
2-wire
Input of cable resistance compensation on a 2-wire RTD connection.
Input: 0.00 to 30.00 Ω
compensation
!
Function is only active when a 2-wire connection has been selected in the device function
SENSOR CONNECTION.
Offset
Input of the zero point correction (offset).
Input: -10.00 to 10.00 °C (-18.00 to 18.00 °F)
0.00 °C
Unit
Display of measurement unit.
Sensor unit = PV unit
Serial no. sensor
Input of the serial number of the sensor connected to this sensor input.
®
Availability in ReadWin
2000, HART
PV lower range value
Input of 4 mA value.
Input: Limitation values see device function SENSOR TYPE.
0 °C
PV upper range value
Input of 20 mA value.
Input: Limitation values see device function SENSOR TYPE.
100 °C
Analog output
Input of the standard (4 to 20 mA) or inverse (20 to 4 mA) current output signal.
Input:
• 4 to 20 mA
• 20 to 4 mA
Filter
Selection of the digital filter 1. order (filter time constant).
Input: 0 to 60 s
HART Output/
Preamble
Multidrop
Device
address
66
Function group SENSOR
Note!
Function group OUTPUT
®
handheld terminal DXR 375 (symbol
Input: Number of response preambles: 5 to 20
5
Input: HART address of the temperature transmitters:
0 to 15
!
Note!
If addresses > 0, the temperature transmitter
is in Multidrop mode and the analogue output is set to 4 mA. Device
address is shown on the display in the Multidrop mode
7
)
TMT142
+
+
+
+
+
+
+
+
7
®
ReadWin
2000
/FieldCare
+
+
+
+
+
+
+
+
-
+
Endress+Hauser