Technical Data - S+S Regeltechnik AERASGARD ACO2 Notice D'instruction

Masquer les pouces Voir aussi pour AERASGARD ACO2:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

G
®
AERASGARD
ACO
The self-calibrating microprocessor-controlled AERASGARD
detect the CO
content in air. This CO
2
without display. The measurement signals are converted into standard signals
of 0 -10 V. Optionally, this CO
switching output. The CO
content in air is determined by a NDIR sensor (non-
2
dis persive infrared technology). The detection range of this CO
brated for standard applications such as monitoring of residential rooms or
conference rooms. Room ventil ation on an as - needed basis, improvement of
well-being and customer benefit, increased comfort as well as a reduction of
operating costs by energy conservation are only some of the beneficial results
®
of employing AERASGARD

TECHNICAL DATA:

Power supply: .............................. 24 V AC ⁄ DC
Sensor: ......................................... optical sensor (NDIR),
Measuring range: ....................... multi-range switching (selectable via jumper)
Output: ......................................... 0 -10 V or with potential-free changeover
Measuring accuracy: ................. ± 100 ppm, ± 5 % of final value
Pressure dependence: .............. ± 1.6 % ⁄ kPa (referred to standard pressure)
Long-term stability: .................... ± 1 % of final value per year
Service life: .................................. > 12 years
Gas exchange: ............................. by diffusion
Ambient temperature: .............. 0 ...+50 °C
Electrical connection: ................ 0.14 - 1.5 mm
Enclosure: .................................... plastic, polyamide,
Dimensions: ................................. 108 x 73.5 x 70 mm
Cable gland: ................................. M16, including strain relief
Protective tube: .......................... metal, Ø 20 mm,
Protection class: ....................... III (according to EN 60 730)
Protection type: ......................... IP 65 (according to EN 60 529)
Standards: .................................. CE-conformity,
Optional: ....................................... 8 - digit display,
Type ⁄ WG1
Measuring Range
CO
2
ACO
0 ... 2000 ppm ⁄ 0 ... 5000 ppm ⁄ 0 ... 10000 ppm
2
ACO
- W
0 ... 2000 ppm ⁄ 0 ... 5000 ppm ⁄ 0 ... 10000 ppm
2
xx - Display
Note:
This unit must not be used as safety-relevant device!
2
sensor is optionally available with or
2
measuring trans ducer can be supplied with
2
ACO
sensors.
2
non-dispersive infrared technology
0 ... 2000 ppm; 0 ... 5000 ppm; 0 ... 10000 ppm
contact (24 V)
2
,
via terminals on circuit board
30 % glass-globe-reinforced,
with quick-locking screws,
colour pure white (similar RAL 9010)
nominal length NL = 130 mm
electromagnetic compatibility
according to EN 61 326 + A1 + A2,
EMC directive 2004 ⁄ 108 ⁄ EC
cutout 36 x14 mm (W x H),
for displaying actual CO
2
(switchable)
®
ACO
is used to
2
Connecting diagram
sensor is cali-
2
Connecting diagram
Schematic diagram
content
Output
CO
0 - 10 V
0 - 10 V
1
UB- GND
2
UB+ supply voltage 24V AC/DC
3
Output 0-10V CO
1
UB- GND
2
UB+ supply voltage 24V AC/DC
3
Output 0-10V CO
Normally open
5
contact
6
7
Breaker
CO
range
2
manu/auto
set CO
2
(ACO -W)
2
7
6
5
CO
content
2
(measuring range adjustable)
0 ... 2000 ppm (default)
0 ... 5000 ppm
0 ... 10000 ppm
Features
2
Changeover contact
ACO
2
-content n ppm
2
ACO
- W
2
-content n ppm
2
ACO
- W
2
ACO
2
3
2
1
JP
JP
JP
1
2
3