5.4
COMBUSTIBLE FACING MATERIAL
WARNING: Combustible facing material must not project more than 4" (101.6mm) from the face of the door
(all four sides). If greater projections are desired, increase the clearance to the sides and top by 2" (50.8mm)
for every additional 1" (25.4mm) of projection. If using an optional surround, the same rule applies, starting
from the top of the surround. Ensure clearances are maintained for surround removal, as it must lift off the
appliance for maintenance.
B
B
3"(76.2mm)
2" (50.8mm)
0" (0mm)
6" (152.4mm)
5" (127mm)
4" (101.6mm)
TOP OF
TOP OF DOOR
OPENING
APPLIANCE
FRONT OF
DOOR
APPLIANCE
71.6
31
EN
W415-1283 / 05.02.14