19.CONNECTION TO THE FLUE

The internal dimensions of the flue must be of maximum 20 x 20 cm, or 20 cm diameter. In case of a bigger flue or bad
functioning (cracks, poor insulation, etc.) insert a stainless steel pipe with adequate diameter, for the entire flue length, from the
bottom to the top. By using adequate tools, check that there is a flue draught of at least 12 PA. Connect the stove to the flue by
using adequate pipes and fittings. Make absolutely sure to install an anti-draught chimney in compliance with current regulations.

20.USEFUL INFORMATION ABOUT CHIMNEYS

The flue must be compliant with current building regulations. The picture below shows how to connect the fume exhaustion pipe
to a pre-existing flue.

21.COMMISSIONING

The stove commissioning can only be carried out after installation and assembling. The device must then be connected to the
power supply, water and fume exhaustion system. The stove's finishing varnish dries after the stove has been used for a couple of
times. During the first few days, the device could cause unpleasant smells. Air out the room to get rid of smells. Remove the tools
stored in the pellet tank during packaging. Make sure there is nothing left inside the tank.

22.FUEL CHARGE

When loading the fuel, make sure the bag containing the pellets doesn't touch the stove. The fuel has to be loaded in the tank,
in the stove upper area. To load the fuel open up the fuel tank lid, wearing adequate protection gloves to avoid burning your skin
when touching the hot parts in the device. In order to avoid the fire to go out, make sure that the level of pellets inside the tank
remains constant. Make sure that the tank lid is always closed. Only open it when loading the fuel. Be careful not to accidentally
insert tools and objects, besides the fuel, inside the fuel tank.

23.MINIMUM DISTANCE FROM FLAMMABLE MATERIAL

Minimum distance from flammable wall in rear air
Minimum distance from flammable wall side air
Minimum distance from flammable in air floor
insulation thickness on the floor
Front distance from flammable materials
Notice d'installation, d'utilisation et d'entretien
YES
P = 200mm
L = 300mm
F =
0mm
0mm
R = 1000mm