4.2
Damper mounting
Adjustment damper
The supplied damper for adjusting the air flow is to be fitted to
the filter's outlet side.
4.3
control box
CONT-A24
Contains a controller card for sequential pulsing of the valves
in the high-efficiency cleaning system. Each magnetic valve is
activated from the control cabinet. After-cleaning with the fan
turned off, "shut-down cleaning", is included as standard.
LED 1: PULSE INDICATOR
LED 2: PAUSE INDICATOR
LED 3: SHUT DOWN CLEANING ACTIVATED.
LED 4: OK RUN
LED 5: REMOTE
Setting of parameters (always before starting up
the filter unit)
• Press SELECT MENU: With "ADJUST + or -" select
NUMBER OF VALVES connected.
• Press SELECT MENU: With "ADJUST + or -" select PULSE
TIME (0.01-9.99 sec.) Normal setting = 0.25 sec.
• Press SELECT MENU: With "ADJUST + or -" select PAUSE
TIME (1 - 999 sec.)
• Press SELECT MENU: With "ADJUST + or -" select
NUMBER OF CYCLES FOR SHUT DOWN CLEANING.
By selecting 000 the shut down function will be off.
This function requires a signal from the fan controller, see
schematics.
• Press SELECT MENU: LED 4 turns on, in the display E1
will appear, cleaning cycle will start.