2.2 Horizontal Terminations
•
Use Table 2.1 for venting guidelines. Figures 2.2 and 2.3 provide a
guide to calculate total vent run.
•
No vertical rise is required with #KPV. The venting can run
horizontal directly off the appliance.
Maximum Elbows
(8) 90° or (16) 45°
Figure 2.4, Horizontal Termination Guide 1
Kozy Power Vent #KPV
Table 2.1, KPV Venting Guidelines
Maximum Total Horizontal
Maximum Vertical Vent Run
Vent Run
60' (18.3 m)
60' (18.3 m)
Do not exceed 60'
Do not exceed 60'
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
Maximum Vertical Drop
Maximum Total Vent Run
Allowed
8' (2.4 m)
100' (30 m)
For every 1' (30 cm) of vertical
drop the maximum total vent
run is reduced by 2' (61 cm)
5