ENGLISH
Now complete the remaining zones. To do this, repeat the following
steps, working towards the central extract unit.
Activate configuration mode for the current zone by pressing
6
'HIGH' on the iAV Control valve.
Select the vent with the highest flow rate.
7
Adjust the flow rate through the vent in step
8
keys on the iAV Control valve.
Measure any remaining vents within the current zone and fine-
9
tune them using the exhaust vent. Work from highest to lowest
flow rate.
Exit configuration mode for the current zone by pressing 'HIGH' on
10
the iAV Control valve.
96
using the arrow
7