Number
Name
4.5.2
Vacuum
(1) Conform outdoor unit liquid valve and gas valve are closed when deflating air.
(2) Follow the instruction to deflate air of unit with vacuum pump.
Number
1
Name
ODU
(3) Turn on vacuum pump, "LO" knob and "HI" knob to vacuum the air of both gas pipe and liquid pipe. If only
one pipe is deflated, the units exist air leading to a little vacuum degree.
(4) When manometers show -0.1MPa(-1bar), vacuum pump still works for 1hour or more to make sure that indoor
unit and connecting pipes don't exist air.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
GMV5 Compact Series VRF Outdoor Unit
Fig.15 The way of connecting pipe
1
2
Outdoor unit
Booster valve
2
3
Gas valve
Liquid valve
3
Nitrogen
Fig.16 Vacuum
4
5
Manometer
"LO" Knob
18
4
5
Gas valve
Liquid valve
6
7
"HI" Knob
Vacuum pump