2 General Introduction

GREE GMV5 Compact series All DC Inverter VRF outdoor units are based on GREE DC Inverter
compressor technology and special designed for the residential apartments, commercial offices and super
markets. And the capacity range of GMV5 Compact series outdoor units is 22.4 kW, 25 kW, and 28 kW.

2.1 Outdoor Unit and Indoor Unit Combination

(1)One outdoor unit can be connected to the maximum 16 indoor units.
(2)The total capacity of indoor units should be in the range of 50%~135% of the capacity of outdoor unit.
4-Way Cassette
(3)As shown in Fig.1, the outdoor unit can be connected to different type of indoor units including 4-way
Cassette IDU, 1-Way Cassette IDU, Wall Type IDU and Duct Type IDU. If one indoor unit is turned on, the
outdoor unit will start and deliver the required cooling capacity to the indoor unit. If all the indoor units are turned
off, the outdoor unit will be stopped.

2.2 Operating Range

Cooling operation
Heating operation
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
GMV5 Compact Series VRF Outdoor Unit
IDU
1-Way Cassette IDU
Fig.1 Outdoor unit and indoor unit combination
ODU
Wall Type IDU
Ambient temperature:10℃~52℃
Ambient temperature:-20℃~27℃
3
Duct Type IDU