GMV5 Compact Series VRF Outdoor Unit
If L≥90m and H≥15m, then :
② When the distance between indoor unit and its nearest manifold exceeds 10m, the liquid pipe size of the
indoor unit whose rated capacity is less than or equal to 5.0KW should be 2 times bigger than before.
(2) Fitting pipe size between Manifolds at indoor unit side is determined by the total capacity of downstream
indoor unit(s).
Fitting pipe between Manifolds
室内分歧管间的配管
ODU
室外机
IDU
室内机
Total capacity of downstream indoor unit(s)
Fitting pipe size between Manifolds at indoor unit side
X(kW)
Gas pipe(mm)
Liquid pipe(mm)
X≤5.6
Φ12.7
Φ6.35
11