Preparation - BEA LZR-MICROSCAN T Mode D'emploi

Masquer les pouces Voir aussi pour LZR-MICROSCAN T:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

PREPARATION

IMPORTANT:
• Verify operation/functionality of door control and operator prior to system installation.
• Proper functionality of LZR-microscan T system relies on proper installation and adjustment.
• Installation with door system, as intended in UL 325, must be verified by installer.
Hub
1
Install hub in door header,
centered, and in an easily
accessible location.
Sensors
1
Sensors are "handed." Determine
if the sensor you are installing is
right-handed or left-handed. The
image here shows a right-handed
sensor.
4
Route Master Sensor Harness
through Door Loop and plug into
sensor at closest port.
NOTES:
1. For left sensor, remove left Blank Endcap OR for right sensor, remove right Blank Endcap.
2. Pull extra Master Sensor Harness slack through Door Loop (away from sensor) before tightening Endcap screws.
Page 4 of 16
Page 4 of 16
2
Plug System Harness into hub port
labeled System. Do not plug in
any other harnesses.
2
Determine on which side of door
Door Loop will be installed. Cut
to shortest length to avoid loop in
detection zone.
5
Affix Door Loop to sensor with
Pass-Through Endcap and three
(3) screws.
2
3
On the sensor to be mounted
on loop side, remove the Blank
Endcap closest to door hinge.
75.5753.14 LZR-MICROSCAN T 20180208
75.5753.14 LZR-MICROSCAN T 20180208
1

Publicité

Table des Matières
loading

Table des Matières