4.5 Installation of Wired Controller

Please refer to User Manual of Wired Controller for the installation details.
Note:
When installation is finished, the unit must be tested and debugged before operation. Please
refer to Instruction Manual of ODU for auto addressing and debugging details.

5 Wiring Work

Notes:
① For personal safety, the air conditioner must be properly grounded.
② Read carefully the voltage indicated on the nameplate before connecting wires. Then connect
wires according to the wiring diagram. Improper wiring will lead to abnormal operation or damage the unit.
③ Power capacity should be large enough. Sectional area of room wires should be above
2
2.5mm
.
④ For unit's power supply, please use specialized branch circuit and specialized power socket.
⑤ All wiring must comply with standards to ensure safe and correct operation.
⑥ Install specialized branch circuit breaker according to related laws and regulations and
electrical standards.
⑦ All wiring must use pressure terminal or single wire. Multi-twisted wire that connects directly
to the wiring board may cause fire hazard.
⑧ Keep the wires away from refrigerant pipe, compressor and fan.
⑨ Do not alter the inner wires of air conditioner. Manufacturer does not assume responsibility
for damage or abnormal operation due to this reason.
⑩ If the unit is installed in places with strong electromagnetic interference, it's recommended
to use twin-twisted shield wire. During wire connection, please pay attention that the metal shield
layer of the twin-twisted wire must be grounded(outer case) in order to prevent the unit from
electromagnetic interference.
Communication line should be separated from the power cord and the connection wire of IDU
11
and ODU.
If the project needs higher static pressure, you can set it through the wired controller.
12
The appliance must be fitted with means for disconnection from the supply mains having
13
a contact separation in all poles that provide full disconnection under overvoltage category III
conditions, and these means must be incorporated in the fixed wiring in accordance with the wiring
rules.
The appliance shall be installed in accordance with national wiring regulations.

5.1 Connection of Wire and Patch Board Terminal

(1) The connection of wire (as shown in fig 5.1.1)
1) Strip about 25mm insulation of the wire end by stripping and cutting tool.
2) Remove the wiring screws on the terminal board.
3) Shape the tail of wire into ring by needle nose plier, and keep the gauge of ring in accordance
with screw.
4) Use the screwdriver for tightening the terminal.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Multi Variable Air Conditioners Duct Type Indoor Unit
Name
Return Air Inlet (with filter)
Canvas Duct
Return Air Duct
No.
4
5
6
17
Name
Indoor unit
Supply Air Duct
Grille

Publicité

Table des Matières
loading

Table des Matières