strengthened to make it level and to prevent it from vibration. You may consult user or constructor for
details.
③ If the ceiling is not strong enough, you can install a beam bracket in a corner and secure the
unit on the beam.

4.1.4 Horizontal Alignment

After the indoor unit is installed, remember to check the horizontal status of the whole unit. It
should be horizontal from front to back and slant 1% from left to right, following the drainage direction,
as shown in Fig 4.1.8.

4.2 Pipe Connection

(1) Direct the flaring of copper pipe to the center of screwed connection and then screw the
flaring nut tight as shown in Fig 4.2.
(2) Use a torque wrench to tighten up the flaring nut until the wrench gives out a click sound.
pipe joint of indoor unit
wrench
(3) The pipe should not be bent too much or it may crack. Use a pipe bender when bending the
pipe.
(4) Use a sponge to wrap the uninsulated connection pipe and the joint. Then tie it tight with a
plastic tape.

4.3 Installation and Test of Drain Pipe

4.3.1 Notice for Installation of Drain Pipe
(1) The drain pipe should be as short as possible and slope downward for at least 1%~2% so that
condensate can drain out easily.
(2) Size of the drainage hose must not be smaller than that of the drain pipe.
(3) Install the drain pipe according to the following diagram and make it insulated. Improper
installation will lead to water leakage and furniture and other objects may get wet.
(4) You can buy local hard PVC pipe as drain pipe. When connecting the pipe, insert the end of
PVC pipe into the drain hole and then tighten it up with a drain hose and cable tie. Do not use
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Level
Fig 4.1.8
flaring nut
pipe joint
torque wrench
Fig 4.2
10
Torque for tightening nut
Pipe diameter (mm)
Ф6.35
Ф9.52
Ф12.7
Ф15.9
Torque (N·m)
15~30
35~40
45~50
60~65